This page is part of archived documentation for openHAB 4.3. Go to the current stable version
# Modbus Binding
This is the binding to access Modbus TCP and serial slaves. RTU, ASCII and BIN variants of Serial Modbus are supported. Modbus TCP slaves are usually also called as Modbus TCP servers.
The binding can act as
- Modbus TCP Client (that is, as modbus master), querying data from Modbus TCP servers (that is, modbus slaves)
- Modbus serial master, querying data from modbus serial slaves
The Modbus binding polls the slave data with a configurable poll period. openHAB commands are translated to write requests.
The binding has the following extensions:
- E3DC
- Helios easyControls
- Modbus Saia Burgess Controls Binding
- Stiebel Eltron ISG
- Studer
- Modbus Sungrow Binding
- SunSpec
The rest of this page contains details for configuring this binding:
{:toc}
# Main Features
The binding polls (or reads) Modbus data using function codes (FC) FC01 (Read coils), FC02 (Read discrete inputs), FC03 (Read multiple holding registers) or FC04 (Read input registers). This polled data is converted to data suitable for use in openHAB. Functionality exists to interpret typical number formats (e.g. single precision float).
The binding can also write data to Modbus slaves using FC05 (Write single coil), FC06 (Write single holding register), FC15 (Write multiple coils) or FC16 (Write multiple holding registers).
# Caveats And Limitations
Please note the following caveats or limitations
- The binding does not act as Modbus slave (e.g. as Modbus TCP server).
- The binding does support Modbus RTU over Modbus TCP, (also known as "Modbus over TCP/IP" or "Modbus over TCP" or "Modbus RTU/IP"), as well as normal "Modbus TCP".
# Background Material
Reader of the documentation should understand the basics of Modbus protocol. Good sources for further information:
- Wikipedia article (opens new window): good read on modbus basics and addressing.
- Simplymodbus.ca (opens new window): good reference as well as excellent tutorial like explanation of the protocol
Useful tools
- binaryconvert.com (opens new window): tool to convert numbers between different binary presentations
- rapidscada.net Modbus parser (opens new window): tool to parse Modbus requests and responses. Useful for debugging purposes when you want to understand the message sent / received.
- JSFiddle tool (opens new window) to test JavaScript (JS) transformations interactively
# Supported Things
This binding supports 4 different things types
Thing | Type | Description |
---|---|---|
tcp | Bridge | Modbus TCP server (Modbus TCP slave) |
serial | Bridge | Modbus serial slave |
poller | Bridge | Thing taking care of polling the data from modbus slaves. One poller corresponds to single Modbus read request (FC01, FC02, FC03, or FC04). Is child of tcp or serial . |
data | Thing | thing for converting polled data to meaningful numbers. Analogously, is responsible of converting openHAB commands to Modbus write requests. Is child of poller (read-only or read-write things) or tcp /serial (write-only things). |
Typically one defines either tcp
or serial
bridge, depending on the variant of Modbus slave.
For each Modbus read request, a poller
is defined.
Finally, one ore more data
things are introduced to extract relevant numbers from the raw Modbus data.
For write-only communication, data
things can be introduced directly as children of tcp
or serial
bridges.
# Binding Configuration
Other than the things themselves, there is no binding configuration.
# Serial Port Configuration
With serial Modbus slaves, configuration of the serial port in openHAB is important. Otherwise you might encounter errors preventing all communication.
See general documentation about serial port configuration to configure the serial port correctly.
# Thing Configuration
In the tables below the thing configuration parameters are grouped by thing type.
Things can be configured using the UI, or using a .things
file.
The configuration in this documentation explains the .things
file, although you can find the same parameters in the UI.
Note that parameter type is very critical when writing .things
file yourself, since it affects how the parameter value is encoded in the text file.
Some examples:
parameter="value"
fortext
parametersparameter=4
forinteger
parameter=true
forboolean
Note the differences with quoting.
Required parameters must be specified in the .things
file.
When optional parameters are not specified, they default to the values shown in the table below.
# tcp
Thing
tcp
is representing a particular Modbus TCP server (slave).
Basic parameters
Parameter | Type | Required | Default if omitted | Description |
---|---|---|---|---|
host | text | "localhost" | IP Address or hostname | |
port | integer | 502 | Port number | |
id | integer | 1 | Slave id. Also known as station address or unit identifier. | |
rtuEncoded | boolean | false | Use RTU encoding instead of regular TCP encoding. |
Advanced parameters
Parameter | Required | Type | Default if omitted | Description |
---|---|---|---|---|
timeBetweenTransactionsMillis | integer | 60 | How long to delay we must have at minimum between two consecutive MODBUS transactions. In milliseconds. | |
timeBetweenReconnectMillis | integer | 0 | How long to wait to before trying to establish a new connection after the previous one has been disconnected. In milliseconds. | |
connectMaxTries | integer | 1 | How many times we try to establish the connection. Should be at least 1. | |
afterConnectionDelayMillis | integer | 0 | Connection warm-up time. Additional time which is spent on preparing connection which should be spent waiting while end device is getting ready to answer first modbus call. In milliseconds. | |
reconnectAfterMillis | integer | 0 | The connection is kept open at least the time specified here. Value of zero means that connection is disconnected after every MODBUS transaction. In milliseconds. | |
connectTimeoutMillis | integer | 10000 | The maximum time that is waited when establishing the connection. Value of zero means that system/OS default is respected. In milliseconds. | |
enableDiscovery | boolean | false | Enable auto-discovery feature. Effective only if a supporting extension has been installed. |
Note: Advanced parameters must be equal for all tcp
things sharing the same host
and port
.
The advanced parameters have conservative defaults, meaning that they should work for most users.
In some cases when extreme performance is required (e.g. poll period below 10 ms), one might want to decrease the delay parameters, especially timeBetweenTransactionsMillis
.
Similarly, with some slower devices on might need to increase the values.
# serial
Thing
serial
is representing a particular Modbus serial slave.
Basic parameters
Parameter | Type | Required | Default if omitted | Description | |
---|---|---|---|---|---|
port | text | ✓ | Serial port to use, for example "/dev/ttyS0" or "COM1" | ||
id | integer | 1 | Slave id. Also known as station address or unit identifier. See Wikipedia (opens new window) and simplymodbus (opens new window) articles for more information | ||
baud | integer | ✓ | Baud of the connection. Valid values are: 75 , 110 , 300 , 1200 , 2400 , 4800 , 9600 , 19200 , 38400 , 57600 , 115200 . | ||
stopBits | text | ✓ | Stop bits. Valid values are: "1.0" , "1.5" , "2.0" . | ||
parity | text | ✓ | Parity. Valid values are: "none" , "even" , "odd" . | ||
dataBits | integer | ✓ | Data bits. Valid values are: 5 , 6 , 7 and 8 . | ||
encoding | text | "rtu" | Encoding. Valid values are: "ascii" , "rtu" , "bin" . | ||
echo | boolean | false | Flag for setting the RS485 echo mode. This controls whether we should try to read back whatever we send on the line, before reading the response. Valid values are: true , false . |
Advanced parameters
Parameter | Required | Type | Default if omitted | Description |
---|---|---|---|---|
receiveTimeoutMillis | integer | 1500 | Timeout for read operations. In milliseconds. | |
flowControlIn | text | "none" | Type of flow control for receiving. Valid values are: "none" , "xon/xoff in" , "rts/cts in" . | |
flowControlOut | text | "none" | Type of flow control for sending. Valid values are: "none" , "xon/xoff out" , "rts/cts out" . | |
timeBetweenTransactionsMillis | integer | 35 | How long to delay we must have at minimum between two consecutive MODBUS transactions. In milliseconds. | |
connectMaxTries | integer | 1 | How many times we try to establish the connection. Should be at least 1. | |
afterConnectionDelayMillis | integer | 0 | Connection warm-up time. Additional time which is spent on preparing connection which should be spent waiting while end device is getting ready to answer first modbus call. In milliseconds. | |
connectTimeoutMillis | integer | 10000 | The maximum time that is waited when establishing the connection. Value of zero means thatsystem/OS default is respected. In milliseconds. | |
enableDiscovery | boolean | false | Enable auto-discovery feature. Effective only if a supporting extension has been installed. |
With the exception of id
parameters should be equal for all serial
things sharing the same port
.
These parameters have conservative defaults, meaning that they should work for most users.
In some cases when extreme performance is required (e.g. poll period below 10ms), one might want to decrease the delay parameters, especially timeBetweenTransactionsMillis
.
With some slower devices on might need to increase the values.
With low baud rates and/or long read requests (that is, many items polled), there might be need to increase the read timeout receiveTimeoutMillis
to e.g. 5000
(=5 seconds).
# poller
Thing
poller
thing takes care of polling the Modbus serial slave or Modbus TCP server data regularly.
You must give each of your bridge Things a reference (thing ID) that is unique for this binding.
Parameter | Type | Required | Default if omitted | Description |
---|---|---|---|---|
start | integer | 0 | Address of the first register, coil, or discrete input to poll. Input as zero-based index number. | |
length | integer | ✓ | (-) | Number of registers, coils or discrete inputs to read. Note that protocol limits max length, depending on type |
type | text | ✓ | (-) | Type of modbus items to poll. This matches directly to Modbus request type or function code (FC). Valid values are: "coil" (FC01), "discrete" (FC02), "holding" (FC03), "input" (FC04). |
refresh | integer | 500 | Poll interval in milliseconds. Use zero to disable automatic polling. | |
maxTries | integer | 3 | Maximum tries when reading. Number of tries when reading data, if some of the reading fail. For single try, enter 1. | |
cacheMillis | integer | 50 | Duration for data cache to be valid, in milliseconds. This cache is used only to serve REFRESH commands. Use zero to disable the caching. |
Polling can be manually triggered by sending REFRESH
command to item bound to channel of data
thing.
When manually triggering polling, a new poll is executed as soon as possible, and sibling data
things (i.e. things that share the same poller
bridge) are updated.
In case the poller
had just received a data response or an error occurred, a cached response is used instead.
See Refresh command section for more details.
Some devices do not allow to query too many registers in a single readout action or a range that spans reserved registers. Split your poller into multiple smaller ones to work around this problem.
# data
Thing
data
is responsible of extracting relevant piece of data (e.g. a number 3.14
) from binary received from the slave.
Similarly, data
thing is responsible of converting openHAB commands to write requests to the Modbus slave.
n.b. note that some numerics like 'readStart' need to be entered as 'text'.
You must give each of your data Things a reference (thing ID) that is unique for this binding.
Parameter | Type | Required | Default if omitted | Description |
---|---|---|---|---|
readValueType | text | (empty) | How data is read from modbus. Use empty for write-only things. Bit value type must be used with coils and discrete inputs. With registers all value types are applicable. Valid values are: "int64" , "int64_swap" , "uint64" , "uint64_swap" , "float32" , "float32_swap" , "int32" , "int32_swap" , "uint32" , "uint32_swap" , "int16" , "uint16" , "int8" , "uint8" , or "bit" . See also Value types on read and write. | |
readStart | text | (empty) | Start address to start reading the value. Use empty for write-only things. Input as zero-based index number, e.g. in place of 400001 (first holding register), use the address "0" . Must be between (poller start) and (poller start + poller length - 1) (inclusive).With registers and value type less than 16 bits, you must use "X.Y" format where Y specifies the sub-element to read from the 16 bit register:
| |
readTransform | text | "default" | Transformation to apply to polled data, after it has been converted to number using readValueType . Use "default" to communicate that no transformation is done and value should be passed as is. Use "SERVICENAME:ARG" or "SERVICENAME(ARG)" (old syntax) to use transformation service SERVICENAME with argument ARG . Any other value than the above types will be interpreted as static text, in which case the actual content of the polled value is ignored. You can chain many transformations with ∩, for example "SERVICE1:ARG1∩SERVICE2:ARG2" . | |
writeValueType | text | (empty) | How data is written to modbus. Only applicable to registers. Valid values are: "int64" , "int64_swap" , "float32" , "float32_swap" , "int32" , "int32_swap" , "int16" . See also Value types on read and write. Value of "bit" can be used with registers as well when writeStart is of format "X.Y" (see below). See also Value types on read and write. | |
writeStart | text | (empty) | Start address of the first holding register or coil in the write. Use empty for read-only things. Use zero based address, e.g. in place of 400001 (first holding register), use the address "0" . This address is passed to data frame as is. One can use "X.Y" to write individual bit Y of an holding X (analogous to readStart ). | |
writeType | text | (empty) | Type of data to write. Use empty for read-only things. Valid values: "coil" or "holding" .Coil uses function code (FC) FC05 or FC15. Holding register uses FC06 or FC16. See writeMultipleEvenWithSingleRegisterOrCoil parameter. | |
writeTransform | text | "default" | Transformation to apply to received commands. Use "default" to communicate that no transformation is done and value should be passed as is. Use "SERVICENAME:ARG" or "SERVICENAME(ARG)" (old syntax) to use transformation service SERVICENAME with argument ARG . Any other value than the above types will be interpreted as static text, in which case the actual content of the command value is ignored. You can chain many transformations with ∩, for example "SERVICE1:ARG1∩SERVICE2:ARG2" . | |
writeMultipleEvenWithSingleRegisterOrCoil | boolean | false | Controls how single register / coil of data is written. By default, or when 'false, FC06 ("Write single holding register") / FC05 ("Write single coil"). Or when 'true', using FC16 ("Write Multiple Holding Registers") / FC15 ("Write Multiple Coils"). | |
writeMaxTries | integer | 3 | Maximum tries when writing Number of tries when writing data, if some of the writes fail. For single try, enter 1 . | |
updateUnchangedValuesEveryMillis | integer | 1000 | Interval to update unchanged values. Modbus binding by default is not updating the item and channel state every time new data is polled from a slave, for performance reasons. Instead, the state is updated whenever it differs from previously updated state, or when enough time has passed since the last update. The time interval can be adjusted using this parameter. Use value of 0 if you like to update state with every poll, even though the value has not changed. In milliseconds. |
# Channels
Only the data
thing has channels.
It has several "data channels", serving the polled data in different formats, and for accepting openHAB commands from different item types.
Please note that transformations might be necessary in order to update some data channels, or to convert some openHAB commands to suitable Modbus data. See Transformations for more details.
Channel Type ID | Item Type | Description |
---|---|---|
number | Number | Data as number |
switch | Switch | Data as switch (ON / OFF ) |
contact | Contact | Data as contact (OPEN / CLOSED ) |
dimmer | Dimmer | Data as dimmer |
datetime | DateTime | Data as a date time |
string | String | Data as string |
rollershutter | Rollershutter | Data as roller shutter |
You can send a REFRESH
command to items linked to any of the above channels to ask binding to explicitly poll new data from the Modbus slave.
See Refresh command section for more details.
Furthermore, there are additional channels that are useful for diagnostics:
Channel Type ID | Item Type | Description |
---|---|---|
lastReadSuccess | DateTime | Last successful read |
lastReadError | DateTime | Last erroring read |
lastWriteSuccess | DateTime | Last successful write |
lastWriteError | DateTime | Last erroring write |
# Item configuration
Items are configured the typical way, using channel
to bind the item to a particular channel.
For example, in the following example, item Temperature_Modbus_Livingroom
is bound to channel number
of thing modbus:data:siemensplc:holding:livingroom_temperature
.
Number Temperature_Modbus_Livingroom "Temperature Living room [%.1f °C]" <temperature> { channel="modbus:data:siemensplc:holding:livingroom_temperature:number" }
Make sure you bind item to a channel that is compatible, or use transformations to make it compatible. See Transformations section for more information on transformation.
# autoupdate
parameter with items
By default, openHAB has autoupdate
enabled.
This means that item state is updated according to received commands.
In some situations this might have unexpected side effects with polling bindings such as Modbus - see example below.
Typically, you see something like this
1 [ome.event.ItemCommandEvent] - Item 'Kitchen_Bar_Table_Light' received command ON
2 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from OFF to ON
3 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from ON to OFF
4 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from OFF to ON
Let's go through it step by step
// openHAB UI switch changed command is sent
1 [ome.event.ItemCommandEvent] - Item 'Kitchen_Bar_Table_Light' received command ON
// openHAB immediately updates the item state to match the command
2 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from OFF to ON
// modbus binding poll completes (old value)
3 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from ON to OFF
// (the binding writes the command over Modbus to the slave)
// modbus binding poll completes (updated value)
4 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from OFF to ON
To prevent this "state fluctuation" (OFF
-> ON
-> OFF
-> ON
), some people prefer to disable autoupdate
on Items used with polling bindings.
With autoupdate
disabled, one would get
// openHAB UI switch changed command is sent
1 [ome.event.ItemCommandEvent] - Item 'Kitchen_Bar_Table_Light' received command ON
// modbus binding poll completes (STILL the old value) -- UI not updated, still showing OFF
// (the binding writes the command over Modbus to the slave)
// modbus binding poll completes (updated value)
4 [vent.ItemStateChangedEvent] - Kitchen_Bar_Table_Light changed from OFF to ON
Item state has no "fluctuation", it updates from OFF
to ON
.
To summarize (credits to rossko57's community post (opens new window)):
autoupdate="false"
: monitor the actual state of deviceautoupdate="true"
: (or defaulted) allows faster display of the expected state in a sitemap
You can disable autoupdate
as follows:
Number Temperature_Modbus_Livingroom "Temperature Living room [%.1f °C]" <temperature> { channel="modbus:data:siemensplc:holding:livingroom_temperature:number", autoupdate="false" }
Main documentation on autoupdate
in Items section of openHAB docs (opens new window).
# Profiles
# modbus:gainOffset
This profile is meant for simple scaling and offsetting of values received from the Modbus slave. The profile works also in the reverse direction, when commanding items.
In addition, the profile allows attaching units to the raw numbers, as well as converting the quantity-aware numbers to bare numbers on write.
Profile has two parameters, gain
(bare number or number with unit) and pre-gain-offset
(bare number), both of which must be provided.
When reading from Modbus, the result will be updateTowardsItem = (raw_value_from_modbus + preOffset) * gain
.
When applying command, the calculation goes in reverse.
See examples for concrete use case with value scaling.
# Discovery
Device specific modbus bindings can take part in the discovery of things, and detect devices automatically. The discovery is initiated by the tcp
and serial
bridges when they have enableDiscovery
setting enabled.
Note that the main binding does not recognize any devices, so it is pointless to turn this on unless you have a suitable add-on binding installed.
# Details
# Comment On Addressing
Modbus Wikipedia article (opens new window) summarizes this excellently:
In the traditional standard, [entity] numbers for those entities start with a digit, followed by a number of four digits in range 1–9,999:
- coils numbers start with a zero and then span from 00001 to 09999
- discrete input numbers start with a one and then span from 10001 to 19999
- input register numbers start with a three and then span from 30001 to 39999
- holding register numbers start with a four and then span from 40001 to 49999
This translates into [entity] addresses between 0 and 9,998 in data frames.
Note that entity begins counting at 1, data frame address at 0.
The openHAB modbus binding uses data frame entity addresses when referring to modbus entities.
That is, the entity address configured in modbus binding is passed to modbus protocol frame as-is.
For example, Modbus poller
thing with start=3
, length=2
and type=holding
will read modbus entities with the following numbers 40004 and 40005.
The manufacturer of any modbus device may choose to use either notation, you may have to infer which, or use trial and error.
# Value Types On Read And Write
This section explains the detailed descriptions of different value types on read and write. Note that value types less than 16 bits are not supported on write to holding registers (see poller thing documentation for details).
See Full examples section for practical examples.
# bit
:
- a single bit is read from the registers
- address is given as
X.Y
, whereY
is between 0...15 (inclusive), representing bit of the registerX
- index
Y=0
refers to the least significant bit - index
Y=1
refers to the second least significant bit, etc.
# int8
:
- a byte (8 bits) from the registers is interpreted as signed integer
- address is given as
X.Y
, whereY
is between 0...1 (inclusive), representing byte of the registerX
- index
Y=0
refers to low byte - index
Y=1
refers to high byte - it is assumed that each high and low byte is encoded in most significant bit first order
# uint8
:
- same as
int8
except value is interpreted as unsigned integer
# int16
:
- register with index is interpreted as 16 bit signed integer.
- it is assumed that register is encoded in most significant bit first order
# uint16
:
- same as
int16
except value is interpreted as unsigned integer
# int32
:
- registers
index
and(index + 1)
are interpreted as signed 32bit integer - it assumed that the first register contains the most significant 16 bits
- it is assumed that each register is encoded in most significant bit first order
# uint32
:
- same as
int32
except value is interpreted as unsigned integer
# float32
:
- registers
index
and(index + 1)
are interpreted as signed 32bit floating point number - it assumed that the first register contains the most significant 16 bits
- it is assumed that each register is encoded in most significant bit first order
# int64
:
- registers
index
,(index + 1)
,(index + 2)
,(index + 3)
are interpreted as signed 64bit integer. - it assumed that the first register contains the most significant 16 bits
- it is assumed that each register is encoded in most significant bit first order
# uint64
:
- same as
int64
except value is interpreted as unsigned integer
The MODBUS specification defines each 16bit word to be encoded as Big Endian, but there is no specification on the order of those words within 32bit or larger data types. The net result is that when you have a master and slave that operate with the same Endian mode things work fine, but add a device with a different Endian mode and it is very hard to correct. To resolve this the binding supports a second set of valuetypes that have the words swapped.
If you get strange values using the int32
, uint32
, float32
, int64
, or uint64
valuetypes then just try the int32_swap
, uint32_swap
, float32_swap
, int64_swap
, or uint64_swap
valuetype, depending upon what your data type is.
# int32_swap
:
- registers
index
and(index + 1)
are interpreted as signed 32bit integer - it assumed that the first register contains the least significant 16 bits
- it is assumed that each register is encoded in most significant bit first order (Big Endian)
# uint32_swap
:
- same as
int32_swap
except value is interpreted as unsigned integer
# float32_swap
:
- registers
index
and(index + 1)
are interpreted as signed 32bit floating point number - it assumed that the first register contains the least significant 16 bits
- it is assumed that each register is encoded in most significant bit first order (Big Endian)
# int64_swap
:
- same as
int64
but registers swapped, that is, registers (index + 3), (index + 2), (index + 1), (index + 1) are interpreted as signed 64bit integer
# uint64_swap
:
- same as
uint64
except value is interpreted as unsigned integer
# REFRESH Command
REFRESH
command to item bound to any data channel makes poller
thing to poll new from the Modbus slave.
All data channels of children data
things are refreshed per the normal logic.
REFRESH
can be useful tool if you like to refresh only on demand (poller
has refresh disabled, i.e. refresh=0
), or have custom logic of refreshing only in some special cases.
Note that poller has cacheMillis
parameter to re-use previously received data, and thus avoid polling the Modbus slave too much.
This parameter is specifically limiting the flood of requests that come when openHAB itself is calling REFRESH
for new things.
# Read Steps
Every time data is read by the binding, these steps are taken to convert the raw binary data to actual item State
in openHAB:
- Poll the data from Modbus slave. Data received is stored in list of bits (discrete inputs and coils), or in list of registers (input registers and holding registers)
- Extract a single number from the polled data, using specified location
readStart
and number "value type"readValueType
. As an example, we can tell the binding to extract 32-bit float (readValueType="float32"
) from register indexreadStart="105"
. - Number is converted to string (e.g.
"3.14"
) and passed as input to the transformation. Note that in casereadTransform="default"
, a default transformation provided by the binding is used. See Transformations section for more details. - For each data channel, we try to convert the transformation output of previous step to a State type (e.g.
ON
/OFF
, orDecimalType
) accepted by the channel. If all the conversions fail (e.g. trying to convertON
to a number), the data channel is not updated.
In case of read errors, all data channels are left unchanged, and lastReadError
channel is updated with current time.
Examples of errors include connection errors, IO errors on read, and explicit exception responses from the slave.
Note: there is a performance optimization that channel state is only updated when enough time has passed since last update, or when the state differs from previous update.
See updateUnchangedValuesEveryMillis
parameter in data
thing.
# Write Steps
# Basic Case
Commands passed to openHAB items that are bound to a data channel are most often processed according to following steps:
- Command is sent to openHAB item, that is bound to a data channel. Command must be such that it is accepted by the item in the first place
- Command is converted to string (e.g.
"3.14"
) and passed to the transformation. Note that in casereadTransform="default"
, a default transformation provided by the binding is used. See Transformations section for more details. - We try to convert transformation output to number (
DecimalType
),OPEN
/CLOSED
(OpenClosedType
), andON
/OFF
(OnOffType
); in this order. First successful conversion is stored. For example,"3.14"
would convert to number (DecimalType
), while"CLOSED"
would convert toCLOSED
(ofOpenClosedType
).' In case all conversions fail, the command is discarded and nothing is written to the Modbus slave. - Next step depends on the
writeType
:writeType="coil"
: the command from the transformation is converted to boolean. Non-zero numbers,ON
, andOPEN
are consideredtrue
; and rest asfalse
.writeType="holding"
: First, the command from the transformation is converted1
/0
number in case ofOPEN
/ON
orCLOSED
/OFF
. The number is converted to one or more registers usingwriteValueType
. For example, number3.14
would be converted to two registers whenwriteValueType="float32"
: [0x4048, 0xF5C3].
- Boolean (
writeType="coil"
) or registers (writeType="holding"
) are written to the Modbus slave usingFC05
,FC06
,FC15
, orFC16
, depending on the value ofwriteMultipleEvenWithSingleRegisterOrCoil
. Write address is specified bywriteStart
.
# Advanced Write Using JSON
There are some more advanced use cases which need more control how the command is converted to set of bits or requests. Due to this reason, one can return a special JSON (opens new window) output from the transformation (step 3). The JSON directly specifies the write requests to send to Modbus slave. In this case, steps 4. and 5. are skipped.
For example, if the transformation returns the following JSON
[
{
"functionCode": 16,
"address": 5412,
"value": [1, 0, 5]
},
{
"functionCode": 6,
"address": 555,
"value": [3],
"maxTries": 10
}
]
Two write requests would be sent to the Modbus slave
- FC16 (write multiple holding register), with start address 5412, having three registers of data (1, 0, and 5).
- FC06 (write single holding register), with start address 555, and single register of data (3). Write is tried maximum of 10 times in case some of the writes fail.
The JSON transformation output can be useful when you need full control how the write goes, for example in case where the write address depends on the incoming command.
Actually, you can omit specifying writeStart
, writeValueType
and writeType
with JSON transformation output altogether.
Empty JSON array ([]
) can be used to suppress all writes.
Explanation for the different properties of the JSON object in the array.
Key name | Value type | Required | Default if omitted | Description |
---|---|---|---|---|
functionCode | number | ✓ | (-) | Modbus function code to use with write. Use one of 5 , 6 , 15 or 16 . |
address | number | ✓ | (-) | Start address of the first holding register or coil in the write. Use empty for read-only things. Use zero based address, e.g. in place of 400001 (first holding register), use the address 0. This address is passed to data frame as is. |
value | JSON array of numbers | ✓ | (-) | Array of coil or register values. Encode coil values as 0 or 1 . |
maxTries | number | 3 | Number of tries when writing data, in case some of the writes fail. Should be at least 1. |
# Transformations
Transformations serve two purpose
readTransform
: doing preprocessing transformations to read binary data and to make it more usable in openHABwriteTransform
: doing preprocessing to openHAB commands before writing them to Modbus slave
Note that transformation is only one part of the overall process how polled data is converted to openHAB state, or how commands are converted to Modbus writes. Consult Read steps and Write steps for more details. Specifically, note that you might not need transformations at all in some uses cases.
Please also note that you should install relevant transformations in openHAB as necessary.
For example, openhab-transformation-javascript
feature provides the javascript (JS
) transformation.
# Transform On Read
readTransform
can be used to transform the polled data, after a number is extracted from the polled data using readValueType
and readStart
(consult Read steps).
There are three different format to specify the configuration:
- String
"default"
, in which case the default transformation is used. The default is to convert non-zero numbers toON
/OPEN
, and zero numbers toOFF
/CLOSED
, respectively. If the item linked to the data channel does not accept these states, the number is converted to best-effort-basis to the states accepted by the item. For example, the extracted number is passed as-is forNumber
items, whileON
/OFF
would be used withDimmerItem
. "SERVICENAME:ARG"
for calling a transformation service. The transformation receives the extracted number as input. This is useful for applying complex arithmetic of the polled data before it is used in openHAB. See examples for more details.- Any other value is interpreted as static text, in which case the actual content of the polled value is ignored. Transformation result is always the same. The transformation output is converted to best-effort-basis to the states accepted by the item.
Consult background documentation on items (opens new window) to understand accepted data types (state) by each item.
# Transform On Write
writeTransform
can be used to transform the openHAB command before it is converted to actual binary data (see Write steps).
There are three different format to specify the configuration:
- String
"default"
, in which case the default transformation is used. The default is to do no conversion to the command. "SERVICENAME:ARG"
for calling a transformation service. The transformation receives the command as input. This is useful for applying complex arithmetic for commands before the data is written to Modbus. See examples for more details.- Any other value is interpreted as static text, in which case the actual command is ignored. Transformation result is always the same.
# Example: Inverting Binary Data On Read And Write
This example transformation is able to invert "boolean" input.
In this case, boolean input is considered to be either number 0
/1
, ON
/OFF
, or OPEN
/CLOSED
.
// function to invert Modbus binary states
// variable "input" contains data passed by openHAB
(function(inputData) {
var out = inputData ; // allow UNDEF to pass through
if (inputData == '1' || inputData == 'ON' || inputData == 'OPEN') {
out = '0' ; // change to OFF or OPEN depending on your Item type
} else if (inputData == '0' || inputData == 'OFF' || inputData == 'CLOSED') {
out = '1' ;
}
return out ; // return a string
})(input)
# Full Examples
Things can be configured in the UI, or using a things
file like here.
# Basic Example
This example reads different kind of Modbus items from the slave.
Please refer to the comments for more explanations.
things/modbus_ex1.things
:
Bridge modbus:tcp:localhostTCP [ host="127.0.0.1", port=502, id=2 ] {
// read-write for coils. Reading 4 coils, with index 4, and 5.
// These correspond to input register numbers 000005, and 000005
Bridge poller coils [ start=4, length=2, refresh=1000, type="coil" ] {
// Note the zero based indexing: first coil is index 0.
Thing data do4 [ readStart="4", readValueType="bit", writeStart="4", writeValueType="bit", writeType="coil" ]
Thing data do5 [ readStart="5", readValueType="bit", writeStart="5", writeValueType="bit", writeType="coil" ]
}
// read-write for holding registers. Reading 4 registers, with index 1500, 1501, 1502, 1503.
// These correspond to holding register numbers 401501, 401502, 401503, 401504.
Bridge poller holding [ start=1500, length=4, refresh=1000, type="holding" ] {
Thing data holding1500 [ readStart="1500", readValueType="float32", writeStart="1500", writeValueType="float32", writeType="holding" ]
Thing data holding1502 [ readStart="1502", readValueType="float32", writeStart="1502", writeValueType="float32", writeType="holding" ]
}
// read-only for input registers. Reading 4 registers, with index 1500, 1501, 1502, 1503.
// These correspond to input register numbers 301501, 301502, 301503, 301504.
Bridge poller inputRegisters [ start=1500, length=4, refresh=1000, type="input" ] {
Thing data input1500 [ readStart="1500", readValueType="float32" ]
Thing data input1502 [ readStart="1502", readValueType="float32" ]
// Extract high or low byte of the 16-bit register as unsigned 8-bit integer (uint8)
Thing data input1502lo [ readStart="1502.0", readValueType="uint8" ]
Thing data input1502hi [ readStart="1502.1", readValueType="uint8" ]
// Extract individual bits of the 16-bit register
// bit 0 is the least significant bit, and bit 15 is the most significant bit
Thing data input1502bit0 [ readStart="1502.0", readValueType="bit" ]
Thing data input1502bit1 [ readStart="1502.1", readValueType="bit" ]
Thing data input1502bit2 [ readStart="1502.2", readValueType="bit" ]
}
// read-only for discrete inputs. Reading 4 discrete inputs, with index 1200, 1201, 1202, 1203.
// These correspond to input register numbers 101201, 101202, 101203, 101204.
Bridge poller discreteInputs [ start=1200, length=4, refresh=1000, type="discrete" ] {
Thing data di1200 [ readStart="1200", readValueType="bit" ]
Thing data di1201 [ readStart="1201", readValueType="bit" ]
}
// Write-only entry: thing is child of tcp directly. No readStart etc. need to be defined.
// Note that the openHAB state might differ from the physical slave since it is not refreshed at all
Thing data holding5write [ writeStart="5", writeValueType="int16", writeType="holding" ]
}
items/modbus_ex1.items
:
Switch DO4 "Digital Output index 4 [%d]" { channel="modbus:data:localhostTCP:coils:do4:switch" }
Switch DO5 "Digital Output index 5 [%d]" { channel="modbus:data:localhostTCP:coils:do5:switch" }
Contact DI1200 "Digital Input index 1200 [%d]" { channel="modbus:data:localhostTCP:discreteInputs:di1200:contact" }
Contact DI1201 "Digital Input index 1201 [%d]" { channel="modbus:data:localhostTCP:discreteInputs:di1201:contact" }
Number Input1500Float32 "Input registers 1500-1501 as float32 [%.1f]" { channel="modbus:data:localhostTCP:inputRegisters:input1500:number" }
Number Input1502Float32 "Input registers 1502-1503 as float32 [%.1f]" { channel="modbus:data:localhostTCP:inputRegisters:input1502:number" }
DateTime Input1502Float32LastOKRead "Input registers 1502-1503 last read [%1$tA, %1$td.%1$tm.%1$tY %1$tH:%1$tM:%1$tS]" { channel="modbus:data:localhostTCP:inputRegisters:input1502:lastReadSuccess" }
DateTime Input1502Float32LastBadRead "Input registers 1502-1503 last read [%1$tA, %1$td.%1$tm.%1$tY %1$tH:%1$tM:%1$tS]" { channel="modbus:data:localhostTCP:inputRegisters:input1502:lastReadError" }
Number Holding5writeonly "Holding index 5 [%.1f]" { channel="modbus:data:localhostTCP:holding5write:number" }
sitemaps/modbus_ex1.sitemap
:
sitemap modbus_ex1 label="modbus_ex1"
{
Frame {
Switch item=DO4
Switch item=DO5
Setpoint item=Holding5writeonly minValue=0 maxValue=100 step=20
Default item=DI1200
Default item=DI1201
Default item=Input1500Float32
Default item=Input1502Float32
Default item=Input1500Float32LastOKRead
Default item=Input1500Float32LastBadRead
}
}
# Writing To Different Address And Type Than Read
This updates the item from discrete input index 4, and writes commands to coil 5. This can be useful when the discrete input is the measurement (e.g. "is valve open?"), and the command is the control (e.g. "open/close valve").
The sitemap shows the current coil status. It also has switches to set/reset coil status, for debugging purposes. Toggling these switches always have the same effect: either setting or resetting the bit.
things/modbus_ex2.things
:
Bridge modbus:tcp:localhostTCPex2 [ host="127.0.0.1", port=502 ] {
Bridge poller items [ start=4, length=2, refresh=1000, type="discrete" ] {
// read from index 4, write to coil 5
Thing data readDiscrete4WriteCoil5 [ readStart="4", readValueType="bit", writeStart="5", writeValueType="bit", writeType="coil" ]
Thing data resetCoil5 [ writeTransform="0", writeStart="5", writeValueType="bit", writeType="coil" ]
Thing data setCoil5 [ writeTransform="1", writeStart="5", writeValueType="bit", writeType="coil" ]
}
Bridge poller coils [ start=5, length=1, refresh=500, type="coil" ] {
Thing data index5 [ readStart="5", readValueType="bit" ]
}
}
items/modbus_ex2.items
:
Switch ReadDI4WriteDO5 "Coil 4/5 mix [%d]" { channel="modbus:data:localhostTCPex2:items:readDiscrete4WriteCoil5:switch" }
Switch ResetDO5 "Flip to turn Coil 5 OFF [%d]" { channel="modbus:data:localhostTCPex2:items:resetCoil5:switch" }
Switch SetDO5 "Flip to turn Coil 5 ON [%d]" { channel="modbus:data:localhostTCPex2:items:setCoil5:switch" }
Contact Coil5 "Coil 5 [%d]" { channel="modbus:data:localhostTCPex2:coils:index5:contact" }
sitemaps/modbus_ex2.sitemap
:
sitemap modbus_ex2 label="modbus_ex2"
{
Frame {
Switch item=ReadDI4WriteDO5
Switch item=ResetDO5
Switch item=SetDO5
Text item=Coil5
}
}
# Scaling Example
Often Modbus slave might have the numbers stored as integers, with no information of the measurement unit. In openHAB, it is recommended to scale and attach units for the read data.
In the below example, modbus data needs to be multiplied by 0.1
to convert the value to Celsius.
For example, raw modbus register value of 45
corresponds to 4.5 °C
.
Note how that unit can be specified within the gain
parameter of modbus:gainOffset
profile.
This enables the use of quantity-aware Number
item Number:Temperature
.
The profile also works the other way round, scaling the commands sent to the item to bare-numbers suitable for Modbus.
things/modbus_ex_scaling.things
:
Bridge modbus:tcp:localhostTCP3 [ host="127.0.0.1", port=502 ] {
Bridge poller holdingPoller [ start=5, length=1, refresh=5000, type="holding" ] {
Thing data temperatureDeciCelsius [ readStart="5", readValueType="int16", writeStart="5", writeValueType="int16", writeType="holding" ]
}
}
items/modbus_ex_scaling.items
:
Number:Temperature TemperatureItem "Temperature [%.1f °C]" { channel="modbus:data:localhostTCP3:holdingPoller:temperatureDeciCelsius:number"[ profile="modbus:gainOffset", gain="0.1 °C", pre-gain-offset="0" ] }
sitemaps/modbus_ex_scaling.sitemap
:
sitemap modbus_ex_scaling label="modbus_ex_scaling"
{
Frame {
Text item=TemperatureItem
Setpoint item=TemperatureItem minValue=0 maxValue=100 step=20
}
}
# Commanding Individual Bits
In Modbus, holding registers represent 16 bits of data. The protocol allow to write the whole register at once.
The binding provides convenience functionality to command individual bits of a holding register by keeping a cache of the register internally.
In order to use this feature, one specifies writeStart="X.Y"
(register X
, bit Y
) with writeValueType="bit"
and writeType="holding"
.
things/modbus_ex_command_bit.things
:
Bridge modbus:tcp:localhostTCP3 [ host="127.0.0.1", port=502 ] {
Bridge poller holdingPoller [ start=5, length=1, refresh=5000, type="holding" ] {
Thing data register5 [ readStart="5.1", readValueType="bit", writeStart="5.1", writeValueType="bit", writeType="holding" ]
Thing data register5Bit1 [ readStart="5.1", readValueType="bit" ]
}
}
items/modbus_ex_command_bit.items
:
Switch SecondLeastSignificantBit "2nd least significant bit write switch [%d]" { channel="modbus:data:localhostTCP3:holdingPoller:register5:switch" }
Number SecondLeastSignificantBitAltRead "2nd least significant bit is now [%d]" { channel="modbus:data:localhostTCP3:holdingPoller:register5Bit1:number" }
sitemaps/modbus_ex_command_bit.sitemap
:
sitemap modbus_ex_command_bit label="modbus_ex_command_bit"
{
Frame {
Text item=SecondLeastSignificantBitAltRead
Switch item=SecondLeastSignificantBit
}
}
# Dimmer Example
Dimmer type Items are not a straightforward match to Modbus registers, as they feature a numeric value which is limited to 0-100 Percent, as well as handling ON/OFF commands.
Transforms can be used to match and scale both reading and writing.
Example for a dimmer device where 255 register value = 100% for fully ON:
things/modbus_ex_dimmer.things
:
Bridge modbus:tcp:remoteTCP [ host="192.168.0.10", port=502 ] {
Bridge poller MBDimmer [ start=4700, length=2, refresh=1000, type="holding" ] {
Thing data DimmerReg [ readStart="4700", readValueType="uint16", readTransform="JS:dimread255.js", writeStart="4700", writeValueType="uint16", writeType="holding", writeTransform="JS:dimwrite255.js" ]
}
}
items/modbus_ex_dimmer.items
:
Dimmer myDimmer "My Dimmer d2 [%.1f]" { channel="modbus:data:remoteTCP:MBDimmer:DimmerReg:dimmer" }
sitemaps/modbus_ex_dimmer.sitemap
:
sitemap modbus_ex_dimmer label="modbus_ex_dimmer"
{
Frame {
Switch item=myDimmer
Slider item=myDimmer
}
}
transform/dimread255.js
:
// Wrap everything in a function (no global variable pollution)
// variable "input" contains data string passed by binding
(function(inputData) {
// here set the 100% equivalent register value
var MAX_SCALE = 255;
// convert to percent
return Math.round( parseFloat(inputData, 10) * 100 / MAX_SCALE );
})(input)
transform/dimwrite255.js
:
// variable "input" contains command string passed by openHAB
(function(inputData) {
// here set the 100% equivalent register value
var MAX_SCALE = 255;
var out = 0
if (inputData == 'ON') {
// set max
out = MAX_SCALE
} else if (inputData == 'OFF') {
out = 0
} else {
// scale from percent
out = Math.round( parseFloat(inputData, 10) * MAX_SCALE / 100 )
}
return out
})(input)
# Rollershutter Example
# Rollershutter
This is an example how different Rollershutter commands can be written to Modbus.
Roller shutter position is read from register 0, UP
/DOWN
commands are written to register 1, and MOVE
/STOP
commands are written to register 2.
The logic of processing commands are summarized in the table
Command | Number written to Modbus slave | Register index |
---|---|---|
UP | 1 | 1 |
DOWN | -1 | 1 |
MOVE | 1 | 2 |
STOP | 0 | 2 |
things/modbus_ex_rollershutter.things
:
Bridge modbus:tcp:localhostTCPRollerShutter [ host="127.0.0.1", port=502 ] {
Bridge poller holding [ start=0, length=3, refresh=1000, type="holding" ] {
// Since we are using advanced transformation outputting JSON,
// other write parameters (writeValueType, writeStart, writeType) can be omitted
Thing data rollershutterData [ readStart="0", readValueType="int16", writeTransform="JS:rollershutter.js" ]
// For diagnostics
Thing data rollershutterDebug0 [ readStart="0", readValueType="int16", writeStart="0", writeValueType="int16", writeType="holding" ]
Thing data rollershutterDebug1 [ readStart="1", readValueType="int16" ]
Thing data rollershutterDebug2 [ readStart="2", readValueType="int16" ]
}
}
items/modbus_ex_rollershutter.items
:
// We disable auto-update to make sure that rollershutter position is updated from the slave, not "automatically" via commands
Rollershutter RollershutterItem "Roller shutter position [%.1f]" <temperature> { autoupdate="false", channel="modbus:data:localhostTCPRollerShutter:holding:rollershutterData:rollershutter" }
// For diagnostics
Number RollershutterItemDebug0 "Roller shutter Debug 0 [%d]" <temperature> { channel="modbus:data:localhostTCPRollerShutter:holding:rollershutterDebug0:number" }
Number RollershutterItemDebug1 "Roller shutter Debug 1 [%d]" <temperature> { channel="modbus:data:localhostTCPRollerShutter:holding:rollershutterDebug1:number" }
Number RollershutterItemDebug2 "Roller shutter Debug 2 [%d]" <temperature> { channel="modbus:data:localhostTCPRollerShutter:holding:rollershutterDebug2:number" }
sitemaps/modbus_ex_rollershutter.sitemap
:
sitemap modbus_ex_rollershutter label="modbus_ex_rollershutter" {
Switch item=RollershutterItem label="Roller shutter [(%d)]" mappings=[UP="up", STOP="X", DOWN="down", MOVE="move"]
// For diagnostics
Setpoint item=RollershutterItemDebug0 minValue=0 maxValue=100 step=20
Text item=RollershutterItemDebug0
Text item=RollershutterItemDebug1
Text item=RollershutterItemDebug2
}
transform/rollershutter.js
:
// Wrap everything in a function
// variable "input" contains data passed by openHAB
(function(cmd) {
var cmdToValue = {"UP": 1, "DOWN": -1, "MOVE": 1, "STOP": 0};
var cmdToAddress = {"UP": 1, "DOWN": 1, "MOVE": 2, "STOP": 2};
var value = cmdToValue[cmd];
var address = cmdToAddress[cmd];
if(value === undefined || address === undefined) {
// unknown command, do not write anything
return "[]";
} else {
return (
"["
+ "{\"functionCode\": 6, \"address\":" + address.toString() + ", \"value\": [" + value + "] }"
+ "]"
);
}
})(input)
# Eager Updates Using REFRESH
In many cases fast enough poll interval is pretty long, e.g. 1 second. This is problematic in cases when faster updates are wanted based on events in openHAB.
For example, in some cases it is useful to update faster when a command is sent to some specific items.
Simple solution is just increase the poll period with the associated performance penalties and possible burden to the slave device.
It is also possible to use REFRESH
command to ask the binding to update more frequently for a short while.
rules/fast_refresh.rules
:
import org.eclipse.xtext.xbase.lib.Procedures
import org.openhab.core.types.RefreshType
val Procedures$Procedure0 refreshData = [ |
// Refresh SetTemperature. In fact, all data things in the same poller are refreshed
SetTemperature.sendCommand(RefreshType.REFRESH)
return null
]
rule "Refresh modbus data quickly after changing settings"
when
Item VacationMode received command or
Item HeatingEnabled received command
then
if (receivedCommand != RefreshType.REFRESH) {
// Update more frequently for a short while, to get
// refereshed data after the newly received command
refreshData()
createTimer(now.plus(100), refreshData)
createTimer(now.plus(200), refreshData)
createTimer(now.plus(300), refreshData)
createTimer(now.plus(500), refreshData)
}
end
Please be aware that REFRESH
commands are "throttled" (to be exact, responses are cached) with poller
parameter cacheMillis
.
# Troubleshooting
Modbus, while simple at its heart, potentially is a complicated standard to use because there's a lot of freedom (and bugs) when it comes to implementations. There are many device or vendor specific quirks and wrinkles you might stumble across. Here's some:
With Modbus TCP devices, there may be multiple network interfaces available, e.g. Wifi and wired Ethernet. However, with some devices the Modbus data is accessible via only one of the interfaces. You need to check the device manufacturer manual, or simply try out which of the IPs are returning valid modbus data. Attention: a device may have an interface with a port open (502 or other) that it responds to Modbus requests on, but that may have no connection to the real bus hardware, resulting in generic Modbus error responses to every request. So check ALL interfaces. Usually either the IP on Ethernet will do.
some devices do not allow to query a range of registers that is too large or spans reserved registers. Do not poll more than 123 registers. Devices may respond with an error or no error but invalid register data so this error can easily go undedetected. Turn your poller thing into multiple things to cover smaller ranges to work around this problem.
there's potentially many more or less weird inconsistencies with some devices. If you fail to read a register or you only ever get invalid values (such as 00 or FF bytes), try with various poller lengths such as the exact length of a register in question or twice the amount. In extreme cases you might even need more than a poller for a single register so you have two or more poller with two or more data things and need to combine these into another item using a rule.
# Changes From Modbus 1.x Binding
The openHAB 1 Modbus binding is quite different from this binding. The biggest difference is that this binding uses things.
Unfortunately there is no conversion tool to convert old configurations to new thing structure.
Due to the introduction of things, the configuration was bound to be backwards incompatible. This offered opportunity to simplify some aspects of configuration. The major differences in configuration logic are:
# Absolute Addresses Instead Of Relative
The new Modbus binding uses absolute addresses. This means that all parameters referring to addresses of input registers, holding registers, discrete inputs or coils are entity addresses. This means that the addresses start from zero (first entity), and can go up to 65 535. See Wikipedia explanation (opens new window) for more information.
Previous binding sometimes used absolute addresses (modbus.cfg
), sometimes relative to polled data (items configuration).
# Register And Bit Addressing
Now 32 bit value types refer start register address. For example valueType="int32"
with start="3"
refers to 32 bit integer in registers 3
and 4
.
The old binding could not handle this case at all since it was assumed that the values were addressed differently.
Read index of 3
would refer to 32 bit integer in registers 3*2=6
and 3*2+1=7
.
It was not possible to refer to 32 bit type starting at odd index.
It is still not possible to read 32 bit value type starting "middle" of register. However, if such need arises the addressing syntax is extensible to covert these cases.
Bits, and other <16 bit value types, inside registers are addressed using start="X.Y"
convention.
This is more explicit notation hopefully reduces the risk of misinterpretation.
# Polling Details
The new binding polls data in parallel which means that errors with one slave do not necessarily slow down polling with some other slave.
Furthermore, once can disable polling altogether and trigger polling on-demand using REFRESH
.
# Transformation Changes
With the new binding the transformations get slightly different input. In polling, the transformation always receives number as input (see Read steps). Old binding had converted the input based on item type.
# Trigger Removed
The old binding had trigger
parameter in item configuration to react only to some openHAB commands, or to some polled states.
There is no trigger anymore but one can use transformations to accomplish the same thing. See Transformations for examples.
# Support For 32, 64 Bit Value Types In Writing
The new binding supports 32 and 64 bit values types when writing.
# How to manually migrate
Here is a step by step example for a migration from a 1.x configuration to an equivalent 2.x configuration. It does not cover all features the 1.x configuration offers, but it should serve as an example on how to get it done.
The 1.x modbus configuration to be updated defined 4 slaves:
modbus.cfg
poll=500
tcp.slave1.connection=192.168.2.9:502
tcp.slave1.type=coil
tcp.slave1.start=12288
tcp.slave1.length=128
tcp.slave1.updateunchangeditems=false
tcp.slave2.connection=192.168.2.9:502
tcp.slave2.type=holding
tcp.slave2.start=12338
tcp.slave2.length=100
tcp.slave2.updateunchangeditems=false
tcp.slave3.connection=192.168.2.9:502
tcp.slave3.type=holding
tcp.slave3.start=12438
tcp.slave3.length=100
tcp.slave3.updateunchangeditems=false
tcp.slave4.connection=192.168.2.9:502
tcp.slave4.type=holding
tcp.slave4.start=12538
tcp.slave4.length=100
tcp.slave4.updateunchangeditems=false
As you can see, all the slaves poll the same modbus device (actually a Wago 750-841 controller).
We now have to create Things
for this slaves.
The 2.x modbus binding uses a three-level definition.
Level one defines a Bridge
for every modbus device that is to be addressed.
The 1.x configuration in this example only addresses one device, so there will be one top level bridge.
Bridge modbus:tcp:wago [ host="192.168.2.9", port=502 ] {
}
Host and Port are taken from the 1.x modbus config.
Within the top level Bridge
there are one or more second level bridges that replace the former slave
configurations.
The poll frequency can now be set per poller
, so you may want to define different poll cycles up to your needs.
The slave Bridge
configs go inside the top level config.
For the four poller
s defined in this example the 2.x configuration looks like this:
Bridge modbus:tcp:wago [ host="192.168.2.9", port=502, id=1 ] {
Bridge poller wago_slave1 [ start=12288, length=128, refresh=500, type="coil" ] {
}
Bridge poller wago_slave2 [ start=12338, length=100, refresh=4000, type="holding" ] {
}
Bridge poller wago_slave3 [ start=12438, length=100, refresh=5000, type="holding" ] {
}
Bridge poller wago_slave4 [ start=12538, length=100, refresh=10000, type="holding" ] {
}
}
Address, length and type can be directly taken over from the 1.x config.
The third (and most complex) part is the definition of data Thing
objects for every Item
bound to modbus.
This definitions go into the corresponding 2nd level Bridge
definitions.
Here it is especially important that the modbus binding now uses absolute addresses all over the place, while the addresses in the item definition for the 1.x binding were relative to the start address of the slave definition before.
For less work in the following final step, the update of the Item
configuration, the naming of the data
things in this example uses the offset of the modbus value within the poller
as suffix, starting with 0(!).
See below for details.
Here a few examples of the Item configuration from the 1.x binding:
The first Item polled with the first poller
used this configuration (with offset 0):
Switch FooSwitch "Foo Switch" {modbus="slave1:0"}
Now we have to define a Thing
that can later be bound to that Item.
The slave1
poller
uses 12288
as start address.
So we define the first data Thing within the poller
wago_slave1
with this address and choose a name that ends with 0
:
Thing data wago_s1_000 [ readStart="12288", readValueType="bit", writeStart="12288", writeValueType="bit", writeType="coil" ]
The second Item of the 1.x binding (offset 1
) is defined as follows.
Switch BarSwitch "Bar Switch" {modbus="slave1:1"}
This leads to the thing definition
Thing data wago_s1_001 [ readStart="12289", readValueType="bit", writeStart="12289", writeValueType="bit", writeType="coil" ]
Note the absolute address 12289
(12288+1) which has to be used here.
Incorporating this definitions into the thing file leads to:
wago.things
:
Bridge modbus:tcp:wago [ host="192.168.2.9", port=502, id=1 ] {
Bridge poller wago_slave1 [ start=12288, length=128, refresh=500, type="coil" ] {
Thing data wago_s1_000 [ readStart="12288", readValueType="bit", writeStart="12288", writeValueType="bit", writeType="coil" ]
Thing data wago_s1_001 [ readStart="12289", readValueType="bit", writeStart="12289", writeValueType="bit", writeType="coil" ]
}
Bridge poller wago_slave2 [ start=12338, length=100, refresh=4000, type="holding" ] {
}
Bridge poller wago_slave3 [ start=12438, length=100, refresh=5000, type="holding" ] {
}
Bridge poller wago_slave4 [ start=12538, length=100, refresh=10000, type="holding" ] {
}
}
Save this in the things
folder.
Watch the file events.log
as it lists your new added data
Things
.
Given that there are no config errors, they quickly change from INITIALIZING
to ONLINE
.
Finally the Item definition has to be changed to refer to the new created data
Thing
.
You can copy the names you need for this directly from the events.log
file:
Switch FooSwitch "Foo Switch" {modbus="slave1:0"}
Switch BarSwitch "Bar Switch" {modbus="slave1:1"}
turn into
Switch FooSwitch "Foo Switch" {channel="modbus:data:wago:wago_slave1:wago_s1_000:switch", autopudate="false"}
Switch BarSwitch "Bar Switch" {channel="modbus:data:wago:wago_slave1:wago_s1_001:switch", autoupdate="false"}
If you have many Items to change and used the naming scheme recommended above, you can now use the following search-and-replace expressions in your editor:
Replace
{modbus="slave1:
by
{channel="modbus:data:wago:wago_slave1:wago_s1_00
in all lines which used single digits for the address in the 1.x config.
Instead of wago
, wago_slave1
and wago_s1_00
you have to use the names you have chosen for your Bridge
, poller
and data
things.
Similar expressions are to be used for two-digit and three-digit relative addresses.
Replace
"}
by
:switch"}
in all lines dealing with switches. For other Item types use the respective replace strings.
That way you can update even a large amount of Item definitions in only a few steps.
The definition of autoupdate
is optional; please refer to autoupdate
to check whether you need it or not.
Continue to add data
Thing
s for all your other Items the same way and link them to your Items.
Save your updated item file and check whether updates come in as expected.
# Troubleshooting Tips
# Thing Status
Check thing status for errors in configuration or communication.
# Enable Verbose Logging
Enable DEBUG
or TRACE
(even more verbose) logging for the loggers named:
org.openhab.binding.modbus
org.openhab.core.io.transport.modbus
net.wimpi.modbus
Consult openHAB logging documentation (opens new window) for more information.
# For Developers
This binding can be extended in many ways. If you have a Modbus enabled device that you want to support in openHAB please read the developer section (opens new window).